Cooling of microprocessors
with micro-evaporation: A novel two-phase cooling cycle
Jackson Braz Marcinichen a,*, John Richard Thome a, Bruno Michel b
aLaboratory
of Heat and Mass Transfer (LTCM), Faculty of Engineering (STI), E´cole
Polytechnique Fe´de´rale de Lausanne (EPFL), Station 9, CH-1015 Lausanne,
Switzerland
b IBM
Research GmbH, Zurich Research Laboratory, Sa¨umerstrasse 4, CH-8803
Ru¨schlikon, Switzerland Dedicated to Professor Dr.-Ing. Dr.h.c.mult. Karl
Stephan on the occasion of his 80th birthday.
a r t i c l e i n f o a b s t r a c t
Article
history:
Received 4 March 2010
Received in revised form 3 June 2010
Accepted 5 June 2010 Available online 12 June 2010
Keywords:
Cooling
Component
Electronic
Microprocessor-design
Comparison
Cooling circuit
COP
Heat recovery
|
Three micro-evaporator cooling cycles, one with a pump, one
with a compressor and a hybrid of the two together, are proposed for cooling
a computer blade server. The hybrid cycle is characterized by the
interchangeability between the first two cycles, where the decision on the
cycle to operate is based on the season (necessity or economical benefit for
heat recovery) or the maintenance of cycle’s driver. The main characteristics
of each cycle are presented as well as the details of the micro-evaporator cooler
for the blade’s CPU. Analysis of the cycle overall efficiency and the
potential for heat recovery shows that the best cycle to use depends mainly
on the end application of the heat recovered. Four refrigerants were
evaluated as the possible working fluids for cooling the microprocessors.
HFC134a and HFC245fa were found to be the best choices for
the desired application. ª 2010 Elsevier Ltd and IIR. All rights reserved.
|
Refroidissement des
microprocesseurs a` l’aide de la microe´vaporation : un cycle de
refroidissement diphasique et innovant
Mots cle´s : Refroidissement
; Composant ; E´lectronique ; Microprocesseur-conception ; Comparaison ;
Circuit frigorifique ; COP ; Re´cupe´ration de chaleur
* Corresponding author.
Tel.: þ41 21 693
5894; fax: þ41 21 693
5960. E-mail address: jackson.marcinichen@epfl.ch (J.B.
Marcinichen).
0140-7007/$ e see front matter ª 2010 Elsevier Ltd and IIR. All
rights reserved. doi:10.1016/j.ijrefrig.2010.06.008
1. Introduction
Cooling of data
centers causes estimated annual electricity bills of 1.4 billion dollars in the
United States and of 3.6 billion dollars world wide (Koomey,
2007). Currently, the most widely used cooling technology is
refrigerated air cooling of the data centers’ numerous servers. According to
recent articles published at ASHRAE Winter Annual Meeting at Dallas (January,
2007) typically 40% or more of the refrigerated air flow bypasses the server
racks in data centers. Furthermore, servers that are turned off or on standby
are cooled as if they were operating, wasting a significant amount of the
energy for the unnecessary flow. This poor energetic performance in one of
industries leading technological sectors is quite startling and motivates the
search for a green thermal solution
for future generations of higher performance servers that consume much less
energy to operate and cool while they also provide the possibility to recover a
large quantity of waste heat. This is the topic of research addressed here.
Current chip cooling technology
consists of conducting the
microprocessor’sJouleheatingawaythroughthesiliconchipdie itself,thenacross a
thermal interface material (TIM) toa copper or aluminum heat spreader/finned
cooling element and finally byconvectiontorefrigeratedairenteringat10e15C.Lookingat
thisonamaterialbasis,themicroprocessorcircuitryhasamass of about 5 mg, the
silicon die about 5 g and the metallic cooling element about 0.5 kg,
representing about five orders of
magnitudeintheratioofthematerialsinvolvedandthuspointsoutthe huge opportunity
to improve this whole process.
Nomenclature
Roman
CHF COP GWP
mr
mw ODP
Psuc
Pdisc
Q
Sub
Tdisc
Tevap_inlet
Tevap_outlet
Tw_inlet
Tw_outlet
Wcompressor
WCond_pump
Wpump
|
critical heat flux [W cm2]
coefficient of performance [-] global warming potential [-] refrigerant mass
flow rate [kgh1] water mass flow rate [kg h1] ozone
depleting potential [-] suction pressure [bar] discharge pressure [bar]
cooling capacity or power generated by electronic components [W] subcooling
[K] discharge temperature [C] inlet evaporating temperature [C]
outlet evaporating
temperature [C]
inlet
water temperature [C] outlet water temperature [C]
compressor
power [W] pumping power of water in the condenser [W] liquid pump power [W]
|
WSubcoole
wv
xoutlet Greek r
Dhcomp DP
DPME DhME hcycle hcycle_LP hcycle_VC
Subscripts
comp
Cond
disc
evap ME
suc
w
|
r_pump pumping power
of water in the
subcondenser [W] volumic
refrigerating effect [kJ m3]
outlet vapor quality [%]
specific mass [kg m3]
compressor enthalpy difference [kJ kg1] pressureincreaseprovided
by the liquid pump[Pa] micro-evaporator pressure drop [bar] specific cooling
capacity [kJ kg1] cycle overall efficiency [-]
liquid pump cycle overall
efficiency [-]
vapor compression cycle
overall efficiency [-]
compressor
condenser discharge evaporating micro-evaporator suction water
|
Thermal designers of data centers
and server manufacturers now agree about the long term need to improve the
cooling process by implementing liquid or two-phase cooling directly in the
server itself, eliminating the poor thermal performing air as a coolant all
together (Greenberg et al., 2006; Hannemann and
Chu, 2007; Samadiani et al., 2008). That said, there is a clear need for
a detailed design and evaluation of these new cooling strategies in order to
arrive at an improved solution. They should provide more efficient heat
transfer from the chips, memories, etc. using water-cooled or boilingcooled
elements, eliminating air as a means of heat transfer, while also reducing
energy consumption for driving the cooling system by a significant amount. Some
examples of design and evaluation of these new cooling strategies can be found
in Scott (1974), Bash (2001), Peeples (2001),
Heydari (2002), Schmidt and Notohardjono (2002), Maveety et al. (2002), Phelan
and Swanson (2004) and Suman et al. (2004).
Additionally, since data centers often dissipate on the order of
5e15 MW of heat, this makes heat
recovery an important
Data center with 64 Blades (Refrigerated air cooling vs. Twophase
on-chip cooling system)
Fig.
1 e
Comparative power supply for a data center containing 64 blades for air
cooled and two-phase on-chip cooling with and without heat recovery.
energetic and environmental issue to
consider and will greatly reduce the CO2 footprint of the data
center.
Fig. 1 shows the
comparative energy consumption required by a data center with 64 blades (325 W
per blade) when using traditional air cooling, two-phase on-chip cooling and
twophase on-chip cooling when the energy is recovered, using a vapor compression
cycle. For air cooling, it is assumed that the power required to cool the data
center is the same as that required to run the information technology equipment
(Koomey, 2007; Ishimine et al., 2009). This
is plotted as a function of the compressor overall efficiency. It is seen that,
if no heatwasrecovered,thecostofcoolingthedatacenterwouldbe approximately 59%
that of traditional air cooling when
operatingatacompressorwithanoverallefficiencyof60%,whichis typical of light
commercial systems. However, if the heat was
toberecoveredandconsidering60%ofrecoveryefficiency,this value drops down to
about 24% that of traditional air cooling. These results show that the cost of
cooling could be drastically decreased when using on-chip cooling, representing
a huge potential for the next generation of data centers cooling systems.
Recent publications show the development of primarily four
competing technologies for cooling chips (all with their own pros and cons):
microchannel single-phase flow, porous media flow, jet impingement cooling and
microchannel twophase flow (Agostini et al., 2007).
Single-phase liquid cooling is now fairly well known and can be used to remove
high heat fluxes. Leonard and Phillips (2005) showed
that the use of such new technology for cooling of chips could produce savings
in energy consumption of over 60%. Despite the potential of this
technology,itsapplicationseemslimitedsofarduetotheneed of a high pumping power
to keep the temperature gradient in the fluid from inlet to outlet within acceptable
limits. Moreover,theworkingfluidmodeledinmoststudiesisusuallypure water, which
presents a problem with its high freezing point, and hence the even higher
pressure drop/pumping power of watereglycol mixtures, the real liquid
working fluid, has to be dealt with for realistic evaluations. Furthermore,
manufacturers are reluctant to use water-based fluids directly in their servers
and mainframes due to reliability questions.
The use of a porous media with single-phase and twophase
flow has as the main advantage of the large surface area for heat transfer.
Nevertheless, a high pumping power remains as a limitation. Jet impingement is
another promising cooling solution that can reach low thermal resistances
without any thermal interface and yield nearly uniform surface temperatures
with multiple jets requiring potentially high pumping power. However, possible
problems related to surface erosion as a consequence of the continuous
impingement of the high velocity jets needs to be further investigated.
Finally, two-phase flow in microchannels, i.e. evaporation
of dielectric refrigerants, is a promising medium to long term solution,
despite the higher complexity involved. This solution consumes a low pumping
power (only 1/10 as much as water cooling according to Hannemann
et al., 2004), has good temperature uniformity (Agostini
et al., 2008), very high heat transfer coefficients (as high as 270 000
W m[1]
K1 according to Madhour et al., in
press), and provides high heat flux dissipation. Studies demonstrate
that the thermal resistance decreases with increasing heat flux and with
decreasing hydraulic diameter. Possible problems with flow instabilities have
been resolved using micro-orifices at the channel inlets (Agostini et al., 2007) while the prediction
methods of local heat transfer coefficients (Consolini
and Thome, 2010), the critical heat flux (Mauro
et al., 2010), and pressure loss (Cioncolini
et al., 2009) in the two-phase region are still improving. On the other
hand, published tests using water evaporating in microchannels to cool computer
chips are not a viable solution (too low absolute pressure and vapor density at
60 C relative to the ensuing pressure drop and speed of sound) and hence this
fluid is not considered here.
Marcinichen and Thome
(2010) showed results of a
simulationcodeforsingle-phaseliquidwaterandtwo-phaseHFC134a cooling cycle, both
with a liquid pump as the driver. The liquid water cooling cycle presented a
pumping power consumption 16.5 times that obtained for the two-phase HFC134a
cooling cycle, considering a design of components and piping so that
thetotalpressuredropinthecyclewasabout1bar.Theresults permitted them to
conclude that the two-phase HFC134a
coolingcyclecanoperateatamuchlowerenergyconsumption compared with a
single-phase liquid water cooling cycle. This result can be considered a
differential when compared with demonstration projects, such as that for the
new supercomputer called AQUASAR (Ganapati, 2009),
which considers the implementation of a liquid water cooling cycle on a rack
cabinet with power consumption of around 10 kW.
In this context, the objective of the present study is
to proposeandanalyzepotentialtwo-phasecoolingcyclesableto maintain the
temperature of the chip below its upper operating limit and to recover energy
from the cycle’s condenser
forexternalapplications,suchasheatingabuilding,residence,
hospital,preheatingofboilerfeedwater,etc.Themainfocusis to work with two-phase
flow of dielectric refrigerants, using a liquid pump or a vapor compressor to
drive the fluid, which can reduce the demand for cooling energy by an
impressive amount compared to the large refrigeration chillers currently used
to cool air in data centers. A specific analysis of the potential working
fluids for this application and the results of critical heat flux obtained with
mathematical models developed for micro-evaporators are presented. Also,
qualitative and quantitative comparisons of the cooling cycles proposed are
made here, using the cycle overall efficiency and the potential for heat
recovery as the factors of merit.
had a mass flow
rate, a pumping power and a condenser size that were 4.6, 10 and 2 times
smaller than the water-cooled system. The coolant temperature rise was 10 C for
the water but negligible for HFC134a. In their study, a demonstration radar
cooling unit was also designed and built for a 6.4 kW heat load (sixteen 400 W
cold plates with convoluted fins). For 25 C ambient air temperature, the
working fluid saturation temperature was maintained at 32 C with a total
volumetric liquid flow rate of 376 L h1 and a cold plate outlet
vapor quality of 30%, providing a safety factor for dry-out. The system was
stable, easily controllable and provided essentially isothermal conditions for
all the cold plates. They emphasized the significant benefits from efficiency,
size and weight that were provided with the PLMC solution.
Mongia
et al. (2006) designed and built a small-scale refrigeration system
applicable for a notebook computer. The system basically included a
minicompressor, a microchannel condenser, a microchannel evaporator and a
capillary tube as the throttling device and is considered to be the first
refrigeration system developed that can fit within the tight confines of a
notebook and operate with high refrigeration efficiencies. HC600a (isobutane)
was the working fluid, chosen from an evaluation of 40 candidate refrigerants.
According to them, HC600a presented the best efficiency at a low pressure ratio
and was readily available, although flammable, but the system required only a
very small fluid charge (a few milliliters). Two evaporators were used, the
first one a microchannel evaporator to cool the high heat flux component (chip)
and the second one a superheater (conventional finned evaporator) to cool lower
heat flux components, such as memories, which also guaranteed that superheated
vapor was delivered to the minicompressor inlet. Two thermal test vehicles were
used to simulate the chip and the power components. For a baseline operating condition,
when the evaporator and condenser temperatures and the heat load were 50 C, 90
C and 50 W, the coefficient of performance (COP)
obtained was 2.25. The COP reached
3.70 when the evaporator and condenser temperatures increased and decreased by
10 C from the baseline conditions and the heat load was reduced to 44 W. The
smallscale refrigeration system achieved 25e30% of the Carnot efficiency (ideal COP for a Carnot cycle), values
comparable with those obtained in today’s household refrigerators.
Trutassanawinetal.(2006)designed,builtandevaluatedthe
performance of a miniature-scale refrigeration system (MSRS)
suitableforelectronicscoolingapplications.TheirMSRShadthe following components:
a commercial small-scale compressor, a microchannel condenser, a manual needle
valve as the expansion device, a cold plate microchannel evaporator, a heat
spreader and two compressor cooling fans. A suction
accumulatortoavoidliquidflowtothecompressor,anoilfiltertoreturn oil to the
compressor and guarantee good lubrication, and heat sources to simulate the
chips were also installed. HFC134a was the working fluid. System performance
measurements were conducted at evaporator temperatures from 10 C to 20 C and
condenser temperatures from 40 C to 60 C. The cooling capacityofthesystemvariedfrom121Wto268WwithaCOPof 1.9e3.2 at pressure ratios of 1.9e3.2.
Their MSRS was able to dissipate CPU heat fluxes of approximately 40e75
W cm2 and keep the junction temperature below 85 C for a chip size
of
1.9 cm2.
It was concluded that a new compressor design for electronics cooling
applications was needed to achieve better
performanceofthesystem(themostsignificantlossesoccurred in the compressor,
which was not designed for the operating conditions of electronics cooling). It
was also recommended to study the development of an automatic expansion device
and a suitable control strategy for the MSRS.
Trutassanawin et al. (2006) also
mentioned some alternative cooling approaches such as heat pipes, liquid
immersion, jet impingement and sprays, thermoelectrics and refrigeration. For
refrigeration, the following possible advantages were cited: (i) one of the
only methods which can work at a high ambient temperature, (ii) chip to fluid
thermal resistances are considerably lower, resulting in lower junction
temperatures, which could lead to higher heat fluxes being dissipated, and
(iii) lower junction temperatures can also increase the microprocessor’s
performance and increase the chip’s reliability. Possible “disadvantages” were
characterized to be: (i) an increase in the complexity and cost, (ii) possible
increase in the cooling system volume and (iii) uncertainties in the system
reliability (moving parts in the compressor).
Thome et al. (2007) surveyed
the advances in thermal modeling for flow boiling of low-pressure refrigerants
in multimicrochannel evaporators for cooling of microprocessors. According to
them, multi-microchannel evaporators hold promise to replace the actual
air-cooling systems and can compete with water cooling to remove high heat
fluxes, higher than 300 W cm2, while maintaining the chip safely
below its maximum working temperature, providing a nearly uniform chip base
temperature (Agostini et al., 2008) and
minimizing energyconsumption.Variablessuchascriticalheatfluxes,flow boilingheattransfercoefficientsandtwo-phasefrictionfactors
were evaluated and characterized as important design parameters to the
micro-evaporator for high heat flux applications.
Thome and Bruch (2008) simulated
two-phase cooling elements for microprocessors with micro-evaporation. Heat
fluxesof50Wcm2 and150Wcm2 inamicro-evaporator with
channels 75 mm wide, 680 mm high and 6 mm long with 100 mm
thick fins were simulated for flow boiling. The size of the chip was assumed to
be 12 mm by 18 mm and the micro-evaporator was considered with the fluid inlet
at the centerline of the chip and outlets at both sides, i.e. a split flow
design to reduce the pressure drop but increase the critical heat flux. Results
of pumping power, critical heat flux, and junction and fluid
temperaturesweregeneratedforHFC134aataninletsaturation temperature of 55 C
(chosen to allow for heat recovery). The
followingconclusionswerereached:i)theinfluenceofmassflux on the fluid, chip and
wall temperatures was small, ii) for the heatflux of 150 W cm2, the
chip temperature was 70C orless,
i.e.wellbelowitsoperationallimitof85C,iii)fortheheatfluxof 150 W cm2,
the junction-to-fluid temperature difference was only 15 K, which is lower than
that with liquid cooling systems, iv)thefluidtemperaturecouldstillberaisedby10Ktoajunction
temperature of 80 C while rejecting heat at 65 C for reuse, and v) the critical
heat flux increased with the mass flux and the lower limit was about 150 W cm2
for 250 kg m2 s1. The channel width had a
significant effect on the wall and junction temperatures, and there was a
turning point at about 100 mm when considering 1000 kg m2 s1
of mass flux and 150 W cm2 of base heat flux, at which these
temperatures reached a minimum. For the same mass flux and base heat flux, the
reduction of channel width also reduced the energy consumption to drive the
flow (pumping power).
From a system viewpoint, Thome
and Bruch (2008) showed an approximate comparison of performances of
liquid water cooling versus two-phase cooling. For the same pumping power
consumption to drive the fluids, two-phase cooling allowed the chip to operate
about 13 K cooler than water cooling or it could operate at the same junction
temperature but consume less pumping power using a lower refrigerant flow rate.
The two-phase cooling system appeared to be more energy-efficient than
classical air-cooling or direct liquid cooling systems while also exhausting the
heat at higher reusable temperatures. Regarding the choice between a pump and a
compressor as the driver for a micro-evaporation heat sink system, they
emphasized that the choice depends on the economic value of the re-used energy.
The system with a compressor is ideal for energy reuse because of the higher
heat rejection temperature; however the additional energy consumed by the
compressor compared to the pump has to be justified by the reuse application.
Mauro et al. (2010) evaluated
the performance of a multimicrochannel copper heat sink with respect to
critical heat flux (CHF ) and
two-phase pressure drop. A heat sink with 29 parallel channels (199 mm
wide and 756 mm deep) was tested experimentally with a split flow system
with one central inlet at the middle of the channels and two outlets at either
end. Three working fluids were tested (HFC134a, HFC236fa and HFC245fa) and also
the parametric effects of mass velocity, saturation temperature and inlet
temperature. The analysis of their results showed that a significantly higher CHF was obtainable with the split flow
system compared to the single inlet-single outlet system (Park and Thome, 2010), providing also a much lower
pressure drop. For the same mass velocity, the increase in CHF exceeded 80% for all working fluids evaluateddueto
theshorterheatedlengthof asplitsystemdesign. For the same total refrigerant
mass flow rate, an increase of 24% for HFC134a and 43% for HFC236fa were
obtained (no comparabledatawereavailableforHFC245fa).Theyconcluded that the
split flow system had the benefit of much larger CHF values with reduced pressuredrops and further developments in
the design of split flow system could yield an interesting energetic solution
for cooling of computer chips. Fig. 2 shows
the details of the two configurations of multi-microchannel copper heat sink
regarding the inlet and outlet flow system.
Fig. 2 e Schematic of micro-evaporator: a)
one inlet/one outlet and b) one inlet/two outlets.
|
Itisworthnotingthatthefocusoftheabovestudieswasthe development
of multi-microchannels evaporators able to
remove “in loco” the heat load generated by
the microprocessors and also the development of two-phase cooling systems able
to: i) control the operating conditions in the micro-evaporator, ii) maintain
the microprocessor temperature at acceptable levels, iii) recover the heat for
a secondary process and iv) operate at a much lower pump energy consumption
compared with a single-phase liquid water cooling system.
3. Present work
Three micro-evaporator cooling cycles are
proposed here:
1. one
with a liquid pump as the driver of the working fluid,
2. one
with a vapor compressor as the driver of the workingfluid, and
3. one
hybrid cycle that is a combination of the first twocycles.
The main characteristics of each cycle are presented below
with a focus on their advantages and the functions of the components.
Additionally some simulations are presented showing the following: (i)
performance of the vapor compression cooling cycle for four refrigerants as the
possible working fluids for cooling the microprocessors, (ii) operational
limits for one specific geometry of a micro-evaporator (critical heat flux,
outlet vapor quality, pressure drop, etc) to demonstrate its suitability for
this type of application, and (iii) potential for heat recovery and the cycle
overall efficiency for the first two cycles proposed.
3.1. Two-phase micro-evaporator cooling
cycle
Figs. 3e5
depict the cycles with a liquid pump, a vapor compressor and hybrid of
these two, respectively. The goal is to control the chip temperature to a
pre-established level by controlling the inlet conditions of the
micro-evaporator (pressure, subcooling and mass flow rate). It is imperative to
keep the micro-evaporator (ME) outlet vapor quality below that of the critical
vapor quality, which is associated with the critical heat flux. Due to this
limitation, additional latent heat is available, which can be used by other
heat generating components. The critical heat flux and outlet vapor quality are
Fig. 3 e Schematic of the liquid pump cooling
cycle.
Fig. 4 e Schematic of the vapor compression
cooling cycle.
predicted using methods developed by Revellin and Thome (2008), which are a function of
micro-evaporator inlet conditions and microchannel dimensions.
Another parameter that must be controlled is the condensing
pressure (condensing temperature). The aim is, during the winter, to recover
the energy dissipated by the refrigerant in the condenser to heat buildings,
residences, district heating, etc. In order to accomplish this, the idea is to
use a variable speed compressor and an electric expansion valve, as will be
discussed below.
Fig. 3 depicts the
two-phase cooling cycle where the flow rate is controlled by a liquid pump. The
P-h diagram (Fig. 6), which was drawn for
low pressure refrigerant HFC245fa, shows the thermodynamic conditions for
specific points along the cooling cycle, considering 9.9 K and 60 C for the
subcooling and evaporating temperature at the ME inlet, respectively. The
pressure drops in the micro-evaporator and microchannel cooling plate for the
memory chips (MPM) were simulated to be on the order of 0.5 bar and
0.0 bar (it is negligible), respectively, based on preliminary calculations.
These values are representative and were defined only for cycle interpretation.
The components considered and their main functions are presented below:
a) Variable
speed liquid pump: controls the mass flow ratecirculating in the system.
b) Stepper
motor valve: controls the liquid flow rate tocontrol the outlet vapor quality
in each micro-evaporator (0%e100%).
c) Micro-evaporator
(ME): transfers the heat generated by themicroprocessor to the refrigerant.
d) Microchannel
cold plate for memories (MPM): additional component used to cool the
memories using the remaining latent heat, which is available due to the
limitations enforced on the micro-evaporator.
e) Pressure
control valve (PCV): controls the condensingpressure.
Fig. 5 e Schematic of the hybrid cooling
cycle highlighting the possibility of interchangeability between liquid pump
and vapor compression cooling cycle.
|
f) Condenser:
counter-flow tube-in-tube exchanger or a micro-condenser.
g) Liquid
accumulator: guarantees that there is only satu-rated liquid at the subcooler
inlet, independent of changes in thermal load.
h) Temperature
control valve (TCV): controls the subcoolingat the inlet of liquid pump.
This cycle is characterized in having low initial costs, a
low vapor quality at the ME outlet, a high overall efficiency, low maintenance
costs and a low condensing temperature. This is a good operating option when
the energy dissipated in the condenser is not recovered, typically during the
summer season. However, the heat can still be recovered if there is an
appropriate demand for low quality heat (low exergy).
Fig. 6 e HFC245fa P-h diagram showing the
thermodynamic conditions for specific points of the liquid pump cooling cycle.
Fig. 4 shows a
two-phase cooling cycle where a vapor compressor is the driver of the working
fluid. The P-h diagram (Fig. 7), which was
also drawn for low pressure refrigerant HFC245fa, shows the thermodynamic
conditions for specific points along the cooling cycle, considering 0.69 K and
60 C for the subcooling and evaporating temperature at the ME inlet,
respectively. The pressure drops in the ME and MPM were considered
to be the same as for the liquid pump cycle above. The components considered
and their main functions are:
a) Variable
speed compressor: controls the ME inlet pressureand consequently the level of
inlet subcooling.
b) Pressure
control valve (PCV): controls the condensingpressure.
c) Condenser: counter-flow tube-in-tube exchanger or
a micro-condenser.
Fig. 7 e HFC245fa P-h diagram showing the
thermodynamic conditions for specific points of the vapor compression cooling
cycle.
Fig. 8 e Effect of superheating at the inlet
of the VSC on the isentropic COP.
d) Liquid
accumulator: guarantees that there is only satu-rated liquid at the internal
heat exchanger (iHEx1) inlet.
e) Internal
heat exchanger liquid line/suction line (iHEx1):increases the performance of
the cooling system. Fig. 8 shows the ratio
of the isentropic COP with
superheating at the inlet of the VSC relative to the saturation COPsat (as defined by Gosney, 1982). Condensing and evaporating
temperatures of 60 C and 90 C were considered, respectively. It is worth noting
that for the four potential working fluids analyzed, the ratio increases with
superheating, although some fluids, such as ammonia, shows decreasing
performance (Gosney, 1982).
f) Electric
expansion valve (EEV): controls the low-pressurereceiver level.
g) Lowpressurereceiver
(LPR):this componentcan be seen asa second internal heat exchanger liquid
line/suction line, which increases the EEV inlet subcooling and allows an
overfeed to the ME since the ME outlet returns to this receiver. The same
analysis considered for the iHEx1 can be considered here, i.e. the LPR
increases the performance of the cooling system as it, together with the iHEx1,
generates the superheating and the subcooling at the inlet of the VSC and EEV,
respectively.
h) Stepper
motor valve: controls the liquid flow rate tocontrol the outlet vapor quality
in each micro-evaporator (0%e100%).
i) Micro-evaporator
(ME): transfers the heat away from the microprocessor.
j) Microchannel
cold plate for memories (MPM): cools thememories.
This cycle is characterized by a high condensing temperature
(high heat recovery potential), a high range of controllabilityof theME
inletsubcooling (characteristic ofsystemswith VSC and EEV), a medium overall
efficiency when compared with the liquid pumping cooling cycle (uncertain,
evaluate potential for heat recovery in the condenser). This is a good
operating option when the energy dissipated in the condenser is recovered for
other use, typically during the winter season when considering a district heating
application (high exergy).
Fig. 5 considers a hybrid
two-phase cooling cycle, i.e. this multi-purpose cooling cycle makes it
possible to interchange the cycles driven by the liquid pump and the vapor
compressor. The change of cycle would be accomplished through the shut off
valves 1e7 (SOV). The decision on the cooling cycle to operate would
depend on demand for the heat recovered, or allow for cycle maintenance (repair
of the compressor or pump). The microprocessors cannot operate without cooling
and thus the interchangeability of the cycles represents a safety mechanism in
case of failure of the pump or compressor. The “cons” of the hybrid cycle would
be mainly the higher initial cost but certainly the advantages (system online
reliability, controllability, cycle interchangeability and flexibility in heat
recovery) may prove to justify the higher initial cost. Furthermore, this
hybrid cycle represents a plugand-play option
where any one of the three cycles can be installed based on the particular
application, minimizing engineering costs.
Fig. 9 e Typical blade with two
microprocessors and a heat generation capacity higher than 300 W.
|
It is worth mentioning that the applicability of these
cooling cycles is not restricted to only one microprocessor but can be applied
to blade servers and clusters, which may have up to 64 blades per rack cabinet.
Each blade, such as that shown in Fig. 9,
can have two (or more) microprocessors with a heat generation capacity higher
than 150 W. If the auxiliary electronics (memories, etc.) on the blade are
included, the total heat generation per blade can be higher than 300 W. Thus,
the microchannel cold plate (MPM) described in the cooling cycles
has the function to cool the auxiliary electronics that can represent about 60%
of the total heat load on the blade, but have a larger surface area compared to
the CPU and thus a lower heat flux.
Finally, when considering an entire rack, a very sizable
heat loadis generated,which representsa good opportunity to recover the heat
rejected. In this case, reuse of the heat removed from the blades for a
secondary application will greatly reduce the CO2 “footprint” of the
system. For example, if we consider a data center with 50 vertical racks, where
each rack has 64 blades and each blade dissipates 300 W, the total potential
amount of heat to be recovered will be 0.96 MW. Such a heat recovery system requires
a secondary heat transfer fluid to pass through all the condensers (either
water or a refrigerant) and then transport the heat to its destination. 3.2. Working fluids
Thepresenceofoil inthe
coolingcycleswouldadverselyaffect the performance of the heat exchangers and
also possibly lead toproblemsofcloggingofsmallcomponentsandgenerationof
contaminants (Marcinichen, 2006). So, for
this reason, these cyclesshoulduse drivercomponents that do not requireoil for
lubrication purposes (that is, an oil free liquid pump and/or an oil free vapor
compressor should be used).
Table 1 shows a
comparison of four refrigerants in relation to their environmental parameters (BNCR35, 2008), where GWP is the global warming potential (ratio of the warming caused by
the substance to the warming caused by a similar mass of carbon dioxide, GWP ¼ 1 for CO2) and ODP is the ozone depleting potential
(ratio of the impact on ozone of a chemical compared to the impactof a
similarmassof CFC11, ODP¼ 1
for CFC11). It is worth noting that the refrigerants considered have an ODP of zero, but still have rather high
values of GWP.
The four working fluids (HFC236fa, HFC245fa, HFC134a and
HC600a-isobutane) were evaluated with regard to COP and the volumic refrigerating effect for the vapor compression
cooling cycle proposed (Fig. 4). The cycle
considers two microchannel cooling components, ME and MPM, the first
to cool the microprocessor (outlet vapor quality set to 30%) and the second to
cool the auxiliary electronics (memories, DC/DC, etc) on the blade
microprocessor (outlet vapor quality set to 90%, which is the estimated value
that considers the blade manufacturer’s information that the auxiliary
components
Table1 eEnvironmental parameters GWPandODP for the four potential
working fluids.
|
Refrigerant GWP (100 year) ODP
|
HFC236fa 6300 0 HFC245fa
950 0
HFC134a 1300 0
HC600a 3 0
|
Table
2 e Boundary conditions
for the working fluids analysis on the vapor compression cooling cycle.
|
1) Condenser
> condensing temperature ¼ 90 C, outlet vapor quality ¼ 0%
2) Micro-evaporator
on chip (ME)
> inlet saturation temperature ¼ 60 C,
>outlet vapor quality ¼ 30%
3) Microchannel
cold plate on memories (MPM)
> outlet vapor quality ¼ 90%
4) Effectiveness
of iHEx1 ¼ 90%
5) Input data
> fluids: HFC245fa, HFC236fa, HFC134a and HC600a
> total pressure drop in the two evaporators
(ME and MPM) ¼ 0.5 bar
6) Outlet
data
> discharge temperature (isentropic compression)
> enthalpy difference in the two evaporators and in the
compressor
> volumic refrigerating effect (qualitative idea of
compressor size)
>COP
|
can represent up to 65% of the total
heat load). It was also considered that iHEx1 has an effectiveness of 90% and
the two microchannel cooling components have a total pressure drop of 0.5 bar.
The volumic refrigerating effect (wv) is determined by calculating the ratio between the
sum of the ME and MPM enthalpy differences and the specific volume
in the compressor suction (Gosney, 1982).
This parameter indicates comparatively the size of compressor for the different
working fluids, i.e. a higher volumetric refrigerating effect means that a
smaller swept volume rate is required for a particular cooling capacity.
Table 3 shows the
results considering the conditions in Table 2.
For this cycle, the COP was
determined by dividing the sum of the ME and MPM enthalpy
differences (DhME) by
the compressor enthalpy difference (Dhcomp).
It can be observed that HFC245fa has the lowest suction and discharge pressures
(Psuc
and Pdisc), which is
advantageous for the compressor and cooling system (allows a less robust construction
that enables material cost savings). However, it also has a lower volumic
refrigerating effect, meaning that a larger compressor will be necessary. The
best working fluid, when looking at the volumic refrigerating effect, is
HFC134a since its value is more than 2 times higher than that of HFC245fa, but
requires operation at a higher Psuc
and Pdisc. It is
worth noting that HC600a (isobutane) has the highest specific cooling capacity
(DhME), as shown in Fig. 10, implying lower mass flow rates for
the same cooling capacity.
Relatively small differences in COP are observed in Table 3 for
the four fluids, showing no significant effect on the choice of the working
fluid. The same can be said about the compressor discharge temperature (Tdisc). The high values of COP observed are justified by the fact
that the thermodynamic analysis does not consider the irreversibilities
inherent in the cycle. However, due to the high evaporating temperatures
considered here (for attaining a high
performance green
HC600a
h,kJ/kg
Fig. 10 e HC600a P-h diagram highlighting the
large specific cooling capacity.
computing solution), the COP values are higher than those found
in household refrigerators and light commercial systems (actual COP about 2 or 3). Finally, it can be
observed that HC600a and HFC134a present the lowest pressure ratios, which is
an advantage because they represent compressors with high volumetric
efficiencies.
Fig. 11
shows the effects of iHEx1 effectiveness and condensing temperature on
the cycle COP. The same conditions
described in Table 2 were considered and
HFC134a was used as working fluid. It can be observed that the COP increases when the iHEX1
effectiveness increases. However, the condensing temperature has a greater
effect on the COP, decreasing with an
increase of condensing temperature. It is worth mentioning that there might be
an optimal condensing temperature to obtain the maximum economical value of
recovered heat for the penalty paid in compressor power consumption.
ME must be able to maintain the
microprocessor’s operating temperature from 70 C to 75 C (83 C is the nominal
maximum operating temperature).
Basedontheaforementionedinformation,Table4showsthe
results obtained by the methods developed to evaluate the performance of the
ME’s. The three-zone model (Thome et al., 2004)
was used for two-phase heat transfer since it was shown to predict many fluids
and geometries with good accuracy (Dupont et al.,
2004), the numerically based model of Revellin
and Thome (2008) was used for critical heat flux calculations and the
homogeneous model was used for two-phase pressure
dropssinceitwasfoundtopredictmicrochannelpressuredrops
withrelativelygoodaccuracy(Ribatskietal.,2006).Themethods
werealsousedtoestimatethemassflowrateintheME.Theheat load was considered to
vary between 90% and 100%, i.e. from 146.25W to162.50 W. The ME inlet
subcooling, Sub, wasfixed at
5 K and two inlet evaporating temperatures, Tevap_inlet, were considered,
50 C and 60 C. The dimensions of the ME were 170mmoffinwidthandchannelwidthand1700mmoffinheight,
with a heated “footprint” of 18.5 mm by 13.5 mm. The working fluid selected for
the present analysis was HFC134a.
The results show that the mass flow rate, mr, to guarantee the cooling
capacity must be from 10.82 kg h1 to 11.90 kg h1 when the
outlet vapor quality, xoutlet,
is 30% and the inlet evaporating temperature is 60 C. For this case the lowest
critical heat flux, CHF, was 141.2 W
cm2, a value well above the actual value of 65 W cm2 (safety
factor of 2.2). However, when the outlet vapor quality was set to 50%, the
smallest CHF was then only 83.1 W cm2,
a value judgedto be too nearto the actual value for the standard blade (65 W cm2)
since the accuracy in predicting CHF is
about 20%. Thus, it is best to consider an outlet vapor quality of 30%. While
not done here, it is also possible to use the one-dimensional numerical method
of Revellin and Thome (2008) to analyze the
CPU die’s power dissipation map to verify the local safety factors in CHF with respect to the local hot spots.
3.4. Analysis of the cycle
overall efficiency and potential for energy recovery
Table 3 e Results of simulations on the vapor compression cooling
cycle/potential working fluids.
|
|
|||||||
|
Dhcomp (kJ kg1)
|
|||||||
HFC236fa
|
8.0
|
110.9
|
15.65
|
7.14
|
2.19
|
104.0
|
4333
|
13.0
|
HFC245fa
|
8.3
|
110.9
|
10.04
|
4.14
|
2.43
|
150.0
|
3010
|
18.1
|
HFC134a
|
7.0
|
119.2
|
32.47
|
16.33
|
1.99
|
112.7
|
7736
|
16.1
|
HC600a
|
8.4
|
111.1
|
16.14
|
8.10
|
1.99
|
250.5
|
4566
|
30.0
|
The overall efficiencies (hcycle) of the proposed cycles were evaluated considering the potential for energy recovery. This is determined by the ratio of the recovered energy in the condenser and subcooler to the energy consumed to drive the working fluid. Some additional terms were also considered to take into account the pumping power of the secondary fluid in the condenser and subcooler. Thus, considering the possible heat recovery in the heat exchangers, hcycle will be influenced by the type of heat recovery application, since different types
Effects of iHEx1 and condenser on the cycle COP
Fig. 11 e Effects of iHEx1 effectiveness and
condensing temperature on the cycle COP.
of condensers, subcoolers and condensing
temperatures could be chosen to maximize hcycle for the particular
situation.
For an ideal case, the power dissipated by the microprocessor
and memories, QMEþMPM,
and the power consumed by the compressor, Wcompressor,
or the liquid pump, Wpump,
are fully recovered in the condenser and subcooler. This also holds for the
power consumed by the pumps associated with the secondary fluid in the
condenser, WCond_pump, and
subcooler, WSubcooler_pump.
The cycle overall efficiency for the liquid pump and vapor compression cycle
can, therefore, be written as:
a) Liquid
pump cyclehcycle LP ¼ QMEþMPM þ Wþpump þ WCond pump þ WSubcooler pump
Wpump WCond pump þ WSubcooler pump
¼ þ þ QMEþMPM (1)
1
Wpump WCond pump þ WSubcooler pump
b)
Vapor compression cycle
QMEþMPM þ WCompressor þ WCond pump
Presently, we are not concerned with
the performance of the secondary system heat exchanger, which will be a
function of its unknown (for now) mass flow rate and fluid properties. As noted
in Eqs. (1) and (2), the hcycle
will depend mainly on the pumping power of the secondary fluid, which in
itself is a function of the type of application of the secondary system (heat
exchanger size, type and properties of the secondary fluid). It is worth noting
that the difference in cycle overall efficiency for the two cycles is in the
denominator. In general, the compressor power is higher than the liquid pump
power, due to the work needed to obtain a differential pressure associated with
the compressor. This could lead to the conclusion that the hcycle
for the liquid pump cycle is always higher than for the vapor compression
cycle. However, the pumping power of the secondary fluid through the condenser
is higher for the liquid pump cycle than for
the other cycle because of the lower condensing temperature, with the
possibility of the opposite to be true. Furthermore, the hcycle
will depend on the efficiency of each component and on the end use of the
energy recovered in the condenser and subcooler.
The results of a simplified analysis evaluating the
potential of heat recovery for the cycles with the liquid pump and the vapor
compressor are depicted in Table 5. To
develop this analysis, the results in the second line of Table 4 were taken into consideration as well as
the following assumptions:
a) water
was considered as the secondary fluid,
b) the
condenser and subcooler water pumping powers werenot considered,
c) the
HFC134a liquid pumping power was determinedthrough Eq. (3)
for 100% liquid pump overall efficiency. The liquid pump inlet
subcooling was considered 10 K and the inlet pressure was considered that at
the ME outlet,
d) the
compressor suction pressure was considered to be thesame pressure as at the ME
outlet and with 10 K of
superheating,
e) the
vapor compression was considered isentropic and100% compressor overall
efficiency, vapor compression cycle,
Table
4 e Operational limits
for one micro-evaporator. HFC134a as working fluid.
|
Boundary conditions in the
micro-evaporator (working fluid: HFC134a)
Tevap_inlet (C) Sub (K) xoutlet (%) Qw mr (Kg h1) DPME (bar) Tevap_outlet (C) CHF (W cm2)
|
50 5 30 162.50 10.82 0.0092 50.0 145.7
60 5 30 162.50 11.90 0.0096 59.9 148.9
50 5 30 146.25 10.28 0.0082 50.0 141.2
60 5 30 146.25 10.82 0.0082 59.9 141.2
50 5 50 162.50 7.03 0.005 50.0 91.9
60 5 50 162.50 7.57 0.005 59.9 91.2
50 5 50 146.25 6.28 0.0045 50.0 83.3
60 5 50 146.25 6.76 0.0043 59.9 83.1
|
Table 5 e Comparative analysis for the liquid pump and vapor compression cooling
cycle regarding heat recovery.
|
Cycle Energy
recovery (W) Tw_inlet (C) Condenser Subcooler
Tw_outlet (C) mw (Kg h1) Tw_outlet (C) mw (Kg h1)
|
Liquid pump 162.5 30 49.9 4.85 49.9 2.18
Vapor compressor 206.7 30 80.0 3.56 e e
|
h) the condenser and subcooler outlet
water temperature was assumed to be 10 K less than the condensing
temperature,
The refrigerant pumping power is thus
calculated as:
m
Wpump ¼DP (3)
r
where m is the mass flow rate, r is
the specific mass and DP is the pressure
increase provided by the pump.
In Table 5, it can be
observed that there is an increase of 27.2% of heat recovery for the vapor
compression cycle (this additional heat is associated with that imparted by the
compressor) while there is an increase of 98% of total water mass flow rate, mw, for the liquid pump cycle
that is associated with a lower water temperature difference in the condenser
and subcooler. The final result shows that the liquid pump cycle will require a
larger pump to circulate water in the condenser and subcooler, i.e. a higher pumping
power and possibly a larger heat exchanger (condenser þ subcooler).
Finally, it is important to remember that the results presented above are only
for a simple example case and that a more detailed analysis considering all
components and their thermal efficiencies needs to be done to better understand
the behaviorand performance of eachcycle and its particular heat recovery
application.
4. Conclusion
1. Three
two-phase cooling cycles for cooling of data centerservers have been proposed
for more energy-efficient cooling of blade server microprocessors and their
memories. The cycles use two-phase boiling in microchannels for removing the
heat from the microprocessors and memories and the heat can be dissipated
either to the ambient or, better, it will be recovered for heating of
buildings, preheating of boiler feed water, etc. This second solution has the
potential to be a key step in the realization of a new generation of green, high performance data centers.
2. To
integrate operating flexibility and higher system operating reliability into
one cooling cycle, include the possibility to recover heat or not, and to
facilitate maintenance while still operating the server’s cooling system, a
hybrid cooling cycle was proposed with interchangeability between the liquid
pump and vapor compression driven cooling cycles. As the cooling of the servers
should have a very high online availability, the interchangeability will
also guarantee uninterrupted operation in
case of forced maintenance of the compressor or the pump.
3. The
vapor compression cooling cycle proposed was considered to determine the best
working fluid for cooling applications of microprocessors and memories. The
analysis took into consideration the following variables: suction and discharge
pressures, volumic refrigerating effect, pressure ratio and COP. Of the four refrigerants
considered, HFC134a and HFC245fa appear to be the best choices.
4. Methods
taken from the literature to evaluate the thermalperformance of the ME’s were
used here to estimate the CHF of the
ME and compare to the total heat flux of a specific blade. For an evaporating
temperature, subcooling and outlet vapor quality of 60 C, 5 K and 30%,
respectively, the predicted CHF was
about 2.2 times the actual maximum heat flux of the blade server using fins
that were 1700 mm high, 170 mm thick and channels 170 mm
wide. This safety factor was considered sufficient since the accuracy in
predicting CHF is about 20%. For an
outlet vapor quality of 50% the factor decrease to only 1.3 times, a value
judged to be too low to guarantee problem free operation.
5. The
micro-evaporator cooling cycles proposed were
analyzedinrelationtothecycleoverallefficiency(hcycle)and the potential for
energy recovery, after the aforementioned constraint of critical heat flux was taken
into account. The qualitative comparison showed that the best cycle, i.e. that
with the highest hcycle, will depend mainly on the end application of
the energy recovered in the condenser and subcooler, which will influence the
design of the cooling cycle and the thermodynamic conditions. A quantitative
comparison showed that the vapor compression cycle is capable of recovering
more energy for a lower water mass flow rate. Also, it was shown that a higher
water temperatureisachievedwiththevaporcompressioncycleduetothe higher
condensing temperature.
Acknowledgements
The Commission for Technology and Innovation
(CTI) contract number 6862.2 DCS-NM entitled “Micro-Evaporation Cooling System
for High Performance Micro-Processors: Development of Prototype Units and
Performance Testing” directed by the LTCM laboratory sponsored this work along
with the project’s industrial partners: IBM Zu¨rich Research Laboratory
(Switzerland) and Embraco (Brazil). J.B. Marcinichen wishes to thank CAPES
(“Coordenac¸a˜o de Aperfeic¸oamento de Pessoal de N´ıvel Superior”) for a one
year fellowship to work at the LTCM laboratory.
r e f e r e n c e s
Agostini, B., Fabbri, M., Park, J.E., Wojtan, L., Thome,
J.R., Michel, B., 2007. State of the art of high heat flux cooling
technologies. Heat Transfer Engineering 28, 258e281.
Agostini, B., Fabbri, M., Thome, J.R., Michel, B., 2008. High
heat flux two-phase cooling in silicon multimicrochannels. IEEE Transactions on
Components and Packaging Technologies 31 (No 3), 691e701.
Bash, C.E., 2001. Analysis of refrigerated loops for electronics
cooling. In: Proceedings Pacific Rim/ASME Int. Electron.
Packag. Tech. Conf. Exhibition (IPACK’01), Kauai, HI, pp.
811e819.
BNCR35, 2008. Overview of New and Alternative Refrigerants.
Market Transformation Programme/Supporting UK Government Policy on Sustainable
Products. http://efficientproducts.defra.gov.uk/product-strategies/subsector/
commercial-refrigeration.
Cioncolini, A., Thome, J.R., Lombardi, C., 2009. Unified
macro-tomicroscale method to predict two-phase frictional pressure drops of
annular flows. International Journal of Multiphase Flow 35, 1138e1148.
Consolini, L., Thome, J.R., 2010. A heat transfer model for
evaporation of coalescing bubbles in micro-channel flow. International Journal
of Heat and Fluid Flow 31, 115e125.
Dupont, V.,
Thome, J.R., Jacobi, A.M., 2004. Heat transfer model for evaporation in
microchannels. Part II: comparison with the database. International Journal of
Heat and Mass Transfer 47, 3387e3401.
Ganapati,
P., 2009. Water-cooled supercomputer doubles as dorm space heater. http://www.wired.com/gadgetlab/2009/06/ibmsupercomputer/
Viewed
June 23.
Greenberg, S., Mills, E., Tschudi, B., 2006. Best Practices
for Data
Centers: Lessons Learned from Benchmarking 22 Data
Centers. ACEEE Summer Study on Energy Efficiency in
Buildings.
Gosney, W.B., 1982. Principles of Refrigeration, first ed.
CambridgeUniversity Press.
Hannemann, R., Chu, H., 2007. Analysis of Alternative Data
Center Cooling Approaches. InterPACK, Vancouver, BC, CA.
Hannemann, R., Marsala, J., Pitasi, M., 2004. Pumped liquid
multiphase cooling. In: Proceedings IMECE e International Mechanical
Engineering Congress and Exposition, Anaheim, CA, USA, paper 60669.
Heydari, A., 2002. Miniature vapor compression refrigeration
systems for active cooling of high performance computers. In:
Proceedings 8th Intersoc. Conf. Thermal Thermomech.
Phenom. Electron. Syst. (I-THERM), pp. 371e378.
Ishimine, J., Ohba, Y., Ikeda, S., Suzuki, M., 2009.
Improving IDC cooling and air conditioning efficiency. Fujitsu Scientific and
Technical Journal 45, 123e133.
Koomey, J.G., 2007. Estimating Total Power Consumption by
Servers in the U.S. and the World. Analytics Press,
Oakland, CA. http://enterprise.amd.com/us-en/AMD-Business/
Technology-Home/Power-Management.aspx
February
15.
Leonard, P.L., Phillips, A.L., 2005. The thermal bus
opportunity e
a
quantum leap in data center cooling potential. Presented at the ASHRAE Annual
Meeting, Denver, CO.
Madhour, Y., Olivier, J., Costa-Patry, E., Paredes, S.,
Michel, B., Thome, J.R. Flow boiling of R134a in a multi-microchannel heat sink
hotspot heaters for energy-efficient microelectronic CPU cooling applications.
IEEE Transactions on Components and Packaging Technologies, in press.
Marcinichen, J.B., 2006. Theoretical and Experimental Study
of the
Physical/Chemical Aspects of Capillary Tubes Clogging by
Adsorption of Polyolesther.
Doctorate Thesis, Thermal Sciences, Mechanical Engineering, Federal University
of Santa Catarina, Floriano´polis, SC, Brazil (in Portuguese).
Marcinichen, J.B., Thome, J.R., 2010. New novel green
computer two-phase cooling cycle: a model for its steady-state simulation. In:
Proceedings of the 23rd International Conference on Efficiency, Cost,
Optimization, Simulation and Environmental Impact of Energy Systems e ECOS2010,
Lausanne, Switzerland.
Mauro, A.W., Thome, J.R., Toto, D., Vanoli, G.P., 2010.
Saturated critical heat flux in a multi-microchannel heat sink fed by a split
flow system. Experimental Thermal and Fluid Science 34, 81e92.
Maveety, J.G., Brown, M.F.W., Chrysler, G.M., Sanchez, E.A.,
2002. Thermal Management for Electronics Cooling using a Miniature Compressor.
In: Proceedings Int. Microelectron.
Packag. Soc. (IMAPS), Denver, CO.
Mongia, R., Masahiro, K., DiStefano, E., Barry, J., Chen, W.,
Izenson, M., Possamai, F., Zimmermann, A., Mochizuki, M.,
2006. Small scale refrigeration system for electronics cooling within a
notebook computer. In: Proceedings ITHERM, San Diego, CA.
Park, J.E., Thome, J.R., 2010. Critical heat flux in
multimicrochannel copper elements with low pressure refrigerants.
International Journal of Heat and Mass Transfer 53, 110e122.
Peeples, J.W., 2001. Vapor compression cooling for high
performance applications. Electronics Cooling 7, 16e24.
Phelan, P.E., Swanson, J., 2004. Designing a mesoscale
vaporcompression refrigerator for cooling high-power microelectronic. In:
Proceedings Inter Soc. Conf. Thermal Thermomech. Phenom. Electron. Syst.
(I-THERM), Las Vegas, NV, pp. 218e223.
Revellin, R., Thome, J.R., 2008. A theoretical model for the
prediction of the critical heat flux in heated microchannels. International
Journal of Heat and Mass Transfer 51, 1216e1225.
Ribatski, G., Wojtan, L., Thome, J.R., 2006. An analysis of
experimental data and prediction methods for two-phase frictional pressure drop
and flow boiling heat transfer in micro-scale channels. Experimental Thermal
and Fluid Science 31, 1e19.
Samadiani, E., Joshi, Y., Mistree, F., 2008. The thermal
design of a next generation data center: a conceptual exposition.
Journal of Electronic Packaging 130.
Schmidt, R.R., Notohardjono, B.D., 2002. High-end server
lowtemperature cooling. IBM Journal of Research and Development 46, 739e751.
Scott, A.W., 1974. Cooling of Electronic Equipment. Wiley,
New York, pp. 204e227.
Suman, S., Fedorov, A., Joshi, Y., 2004.
Cryogenic/sub-ambient cooling of electronics: revisited. In: Proceedings Inter
Soc.
Conf. Thermal Thermomech. Phenom. Electron. Syst.
(I-THERM), Las Vegas, NV, pp. 224e231.
Thome, J.R., Agostini, B., Revellin, R., Park, J.E., 2007.
Recent advances in thermal modeling of micro-evaporators for cooling of
microprocessors. In: Proceedings of the ASME International Mechanical
Engineering Congress and Exposition (IMECE), Seattle, Washington.
Thome, J.R., Bruch, A., 2008. Refrigerated cooling of
microprocessors with micro-evaporation heat sinks: new development and energy
conservation prospects for green datacenters. In: Proceedings Institute of
Refrigeration (IOR).
Thome, J., Dupont, V., Jacobi, A., 2004. Heat transfer model
for evaporation in microchannels. Part I: presentation of the model.
International Journal of Heat and Mass Transfer 47, 3375e3385.
Trutassanawin,
S., Groll, E.A., Garimella, S.V., Cremaschi, L., 2006. Experimental
investigation of a miniature-scale refrigeration system for electronics
cooling. IEEE Transactions on Components and Packaging Technologies 29 (No. 3),
678e687.
Hannemann
et al. (2004) have proposed a pumped liquid multiphase cooling system
(PLMC) to cool microprocessors and microcontrollers of high-end devices such as
computers, telecommunications switches, high-energy laser arrays and high-power
radars. According to them, their system could handle applications with 100 W
heat loads (single computer chip) as well as applications with short time
periods of kW heat loads (radar). Their PLMC consisted basically of a liquid
pump, a high performance cold plate (evaporator) and a condenser with a low
acoustic noise air mover to dissipate the heat in the ambient air. A comparison
between a singlephase liquid loop (water) and the system proposed with HFC134a
wasmadefor a 200 Wheat load. The HFC134asystem
To evaluate the performance of the cooling
cycles proposed, the first step was to define a standard blade model where we
need to control the microprocessor and memory temperatures. A photograph of the
standard blade is shown in Fig. 9. According
to the manufacturer, when we consider only one microprocessor and the auxiliary
electronics associated with it, the maximum heat flux will be about 65 W cm2
and the area for heat transfer is about 2.5 cm2 (this is the
worst case, i.e. the entire heat load assumed to be concentrated on the small
area of the chip and its ME). Thus the maximum heat transfer rate will be 162.5
W per ME. The cooling capacity per
Tidak ada komentar:
Posting Komentar